Fluke 43B Power Quality Analyser Data[Read More]
[Read Less] C/w Free Calibration Certificate Traceable to National Standards

Fluke 43B Power Quality Analyser. Circuit breakers that trip, transformers that overheat, motors that burn out, machines that don't function properly; whatever the problem, you can quickly and easily identify the cause with the Fluke 43B Power Quality Analyser.
As a Power Quality Analyser it is optimized for industrial measurements on the 50 Hz fundamental frequency. Because its frequency range extends from 10 to 400 Hz, it's also ideal for aviation, marine and railway applications.
Besides the unique extended frequency range, the Fluke 43B is the only instrument that combines the capabilities of a Power Quality Analyser, a 20 MHz oscilloscope, a multimeter and data recorder in a single tool.
| Specifications
|
|
Usable Bandwidth: Harmonics on 400Hz fundamental: Typical accuracy for 400Hz fundamental: |
10 Hz..3.5 9th kHz5% |
|
Usable Bandwidth: Harmonics on 400Hz fundamental: Typical accuracy for 400Hz fundamental: |
20 Hz..2 kHz 5th 10% |
|
Usable Bandwidth: Harmonics on 400Hz fundamental: Typical accuracy for 400Hz fundamental: |
10 Hz..3.5 kHz 9th 10% channel 1, 50% channel 2 |
|
Accuracies are stated as ± (percentage of reading + counts) without probes unless otherwise noted. Specifications below are valid for signals with a fundamental between 40 and 70 Hz. |
|
Input impedance Voltage rating |
1 MΩ, 20 pF 600V rms, CAT III |
|
True-rms voltage (ac + dc) Ranges: Accuracy:
True-rms current (ac + dc) Ranges: Accuracy:
Frequency Ranges: Accuracy: CF Crest factor Ranges: Accuracy: |
5.000 V, 50.00 V, 500.0 V, 1250 V* ±(1% + 10 counts)
50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA ±(1% + 10 counts)
40.0 to 15.9 kHz ±(0.5% + 2 counts)
1.0 - 10.0 ±(0.5% + 1 count) |
|
Watts, VA, VAR
Ranges:
Accuracy:
Accuracy:
Power Factor
Range:
Accuracy:
Displacement Power Factor, Cos .F
Range:
Accuracy:
Range:
Accuracy:
Frequency Fundamental
Ranges:
Accuracy:
|
1-phase and 3-phase,3 conductor balanced loads 250 W - 1.56 GW ±(4% + 4 counts) Fundamental Power ± (2 % + 6 counts) Total Power
0 - 1.0 ±0.04
0.25 - 0.9 ±0.04 0.90 - 1.0 ±0.03
40.0 to 70.0 Hz ±(0.5% + 2 counts)
|
|
Voltage, Current, Frequency
Ranges:
Accuracy:
Fundamental:
2 to 31st harmonic:
32 to 51st harmonic:
Frequency Fundamental
Ranges:
Accuracy:
Phase
Range:
Accuracy:
Range:
Accuracy:
K-factor (Current and Power)
Range:
Accuracy:
THD Total Harmonic Distortion
Range:
Accuracy:
|
Fundamental to 51st harmonic
VA ±(3% + 2 counts) W ±(5% + 2 counts) VA ±(5% +3 counts) W ±(10% +10 counts) VA ±(15% +5 counts) W ±(30% +5 counts)
40 Hz to 70 Hz
±0.25 Hz
V, A (between Fundamental & Harmonics) ±3º to ±15º
W (between Voltage Fundamental & Current Harmonics) ±5º to ±15º
1.0 to 30.0 ±10%
0.00 - 99.99 ±(3% + 8 counts)
|
|
Recording times:
Vrms Actual, Vrms max, min(AC + DC)
Ranges:
Accuracy:
Arms Actual, Arms max, min (AC + DC)
Ranges:
Accuracy: |
4 min to 16 days (selectable)
5.000V, 50.00V, 500.0V, 1250V* Readings ±(2% +10 counts); Cursor readings ± (2% + 12 counts)
50.00A, 500.0A, 5.000 kA, 50.00 kA
±(2% +10 counts)
|
|
Minimum pulse width:
Useful bandwidth input 1:
Number of transients:
Voltage threshold settings:
|
40 ns DC to 1 MHz 40 20%, 50%, 100%, 200% above or below reference
|
|
Resistance ranges:
Resistance accuracy:
Capacitance ranges:
Capacitance accuracy:
Diode voltage:
Continuity:
Max current:
|
500.0 Ω, 5.000 kΩ, 50.00 kΩ, 500.0 kΩ, 5.000 MΩ, 30.00 MΩ ±(0.6% + 5 counts) 50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF ±(2% + 10 counts) Accuracy ±(2% + 5 counts) Beeper on at < 30 Ω ± 5 Ω 0.5 mA
|
|
Inrush times: Current ranges: Accuracy:
|
1 s, 5 s, 10 s, 50 s, 100 s, 5 min 1 A, 5 A, 10 A, 50 A, 100 A, 500 A, 1000 A ±5% of full scale
|
- Temperature (with accessory)
|
Range:
Accuracy:
|
-100 °C - 400 °C ±(0.5% + 5 counts)
|
|
Measurements:
Time ranges:
Max sampling rate:
Bandwidth
Voltage channel [1]:
Current channel [2]:
Coupling:
Vertical sensitivity:
Vertical resolution:
Record length:
Timebase modes:
Pre-trigger:
Trigger Source:
Trigger Mode:
Connect-and-View:
|
dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle, phase, pulse width, crest factor 20 ns/div to 60 s/div 25 MS/s
20 MHz at inputs, 20 MHz with VPS40 probe (included with Fluke43B), 1 MHz with TL24 Leads 15 kHz at inputs, 10 kHz with included clamps AC, DC (10 Hz - 3 dB) 5 mV/div to 500V/div 8 bit (256 levels) 512 samples per channel Normal, roll, single Up to 10 divisions Input 1 or Input 2 or automatic selection Automatic Connect-and-View, Free Run, and Single Shot Advanced automatic triggering that recognizes signal patterns. Automatically adjusts triggering, timebase and amplitude and displays stable pictures
|
|
20 (screens, settings, data)
|
|
Recording times:
Parameters:
|
4 min to 16 days (selectable)
Choose one or two parameters from one of the groups below:
Volts/Ampères/Hertz
Watts, VA, VAR, PF, DPF, Frequency
Harmonics, THD, Volts (Fund. & Harmonic), Ampères (F&H) Watts(F&H)
Frequency (H), %(H) of total, Phase(H), KF
Temperature
Resistance, Diode, Continuity, Capacitance
Scope: DC Voltage, DC Current, AC Voltage, AC Current, Frequency,
Pulse Width + or -, Phase, Duty cycle + or -, Peak max, Peak min, Peak min-max, Crest Factor
|
|
*Rated EN 61010-1 600 V CAT II CSA |
| Environmental Specifications |
| Operating Temperature |
0 °C to +50 °C |
| Safety Specifications |
Electrical Safety |
EN 61010-1 CAT II, 600V. CSA listed |
| Mechanical & General Specifications |
| Size |
232 x 115 x 50 mm |
| Weight |
1.1 kg |
| Warranty |
3 years |
| Battery Life |
Rechargeable Ni-MH pack (charger included)
Operating time:
Charging time: |
6.5 hours
7 hours |
| Shock & Vibration |
Mil 28800E, Type 3, Class III, Style B |
| Case |
IP51 (dust, drip, waterproof) |

|